LUMEN OUTPUT
(1) lamp 650 lumens
(2) lamps 325 lumens each lamp
LAMPS OPERATED
10-42 Watt 4-pin
Rapid Start Compact Lamps, including Twin Tube, Triple Tube, Quad, 2D & Straight
EMERGENCY OPERATION
90 Minutes
The I-42-EM-A Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-42-EM-A switches to the emergency mode and operates one or two of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can. The I-42-EM-A can be used with most 10-42 watt, 4-pin, quad and triple tube compact fluorescent lamps, with an initial output of up to 650 lumens for one lamp.
The I-42-EM-A is provided with 3/8" flex for wiring to the fixture or ballast compartment. The test switch, charge light, and unit battery connector are installed in a standard switch box, which is connected to the I-42-EM-A via 3/8" flex. The switch box is mounted in the ceiling adjacent to the fixture. The I-42-EM-A is designed to be mounted on the fixture or in the ceiling adjacent to the fixture, and is U.L. Listed for factory installation or retrofit applications.
People Also Purchased | ||||
|
||||